TigerOne Access Control Standards
To ensure a secured access environment, Clemson University’s Access Control Standards are to be followed to the maximum extent possible and everywhere technically feasible any time a card access system is being installed or changed. TigerOne must be included in the review of and approve all new card access systems and changes to existing systems prior to installation to ensure compliance with these standards.
Software and System Requirements
Clemson University uses Genetec Access Control System and all card reader installations must interface with this system while supporting the use of the TigerOne ID in both the physical and mobile formats.
Hardware Locations and Requirements
Doors
Exterior doors
- Main and Service entrances to the building must be equipped with an electric lock controlled by a card reader. Where banks of multiple doors occur, only one door needs to be equipped with a card reader. Others may be electrically locked only. Where a powered door operator is in place, that door must always be equipped with a card reader.
- Entrances that need to be open for normal public access but do not need after-hours access must be equipped with an electric lock but may omit a card reader.
- All other exterior doors such as emergency exits, roll up doors, etc. must be configured with mechanical locking hardware only. The door hardware must be configured remain locked from the exterior of the building while providing free egress when required. Optionally, emergency exit doors may also be equipped with a delayed egress alarm system when approved by the University Building Official.
Interior doors
- Card Access: The following points of ingress must have an electric lock controlled by a card reader:
- Instructional spaces including classrooms and teaching labs
- Data Closets
- Mechanical Rooms
- Electrical Rooms
- Entrances that need to be open for normal public access but do not need after-hours access must be equipped with an electric lock but may omit a card reader.
Door position monitoring
- All electrified and perimeter doors must also be equipped with a magnetic contact allowing monitoring of the door position.
Mechanical Key Access
- All doors equipped with electric locks must also be provided with a cylinder for key override/emergency access. All locks must use University standard cylinders.
Intercoms
When a space needs to be secured but accessed by the public, an intercom may be installed to communicate and allow passthrough. Intercom implementations must be paired with a CU VoIP connection. All intercom video streams must also integrate with Genetec.
Products and Materials
Card Readers
- HID R40
- HID R15
- HID Signo 40
- HID Signo 20
All readers must have Bluetooth NFC capability and must be ordered with Clemson programming for NFC and support HID Elite iClass SE and Elite SEOS. Any reader technology that deviates from the above supported models must be sent to TigerOne for system compatibility testing and approval before application.
Intercoms
- 2N IP Verso Series
Any intercom technology that deviates from the above supported model must be sent to TigerOne for system compatibility testing and approval before application.